City of Morgan Hill Water System Master Plan 2017
Table 7.3 Future Storage Requirements Water System Master Plan City of Morgan Hill
PRELIMINARY
Future Water Demands
Future Water Storage Requirements
Pressure Zone
Average Day Demand
Maximum Day Demand
Operational at 25%
Emergency at 25%
Fire Protection
Operational + Emergency
Total, By Pressure Zone
(MG)
(MG)
(MG)
(MG)
(MG)
(MGD)
(MGD)
Central Zones (Nob Hill and Boys Ranch Pressure Zones) Nob Hill Zone 1 2.10 4.20
1.05
1.05
0.63
2.10
2.73
Boys Ranch Zone
0.85
1.70
0.42
0.42
0.63
0.85
1.48
Subtotal
2.95
5.90
1.48
1.48
1.26
2.95
4.21
West Side Pressure Zones
Llagas Zone
0.10
0.21
0.05
0.05
0.18
0.10
0.28
Woodland Zone
0.004
0.008
0.002
0.002
0.18
0.004
0.18
Glen Ayre Zone
0.003
0.007
0.002
0.002
0.18
0.003
0.18
El Toro Zone 2
0.02
0.05
0.01
0.01
0.18
0.02
0.20
Encino Zone
0.02
0.03
0.01
0.01
0.18
0.02
0.20
Subtotal
0.15
0.30
0.08
0.08
0.90
0.15
1.05
East Side Pressure Zones
Holiday Lake Zone
0.007
0.015
0.004
0.004
0.18
0.007
0.19
Holiday 1,2,3 Zones
0.21
0.42
0.11
0.11
0.18
0.21
0.39
Jackson Oaks Zone
0.02
0.04
0.01
0.01
0.18
0.02
0.20
Subtotal
0.24
0.48
0.12
0.12
0.54
0.24
0.78
Total Future Storage Requirements
6.04
3.34
6.68
1.67
1.67
2.70
3.34
8/16/2017
Notes:
1. Nob Hill Zone includes Easy Street Zone demands. 2. El Toro Zone includes Peak and Main Zone and Spring Hill Zone demands.
Made with FlippingBook flipbook maker