City of Morgan Hill Water System Master Plan 2017
Table 4.1 Existing Groundwater Supply Capacity Water System Master Plan City of Morgan Hill
PRELIMINARY
Current Actual Production 1
Design Capacity
Additional Information
Supply Well
Date Drilled
Ground Elevation
Rated
Summer
Winter
Average
HP
Head
(gpm)
(MGD)
(gpm)
(MGD)
(gpm)
(MGD)
(gpm)
(MGD)
(ft)
(HP)
(ft)
(ft)
Boys Ranch Pressure Zone (HWL = 563 feet) Boys Ranch # 1 1,500 2.16
346
0.5
387
0.6
367
0.5
380
1982
150
384
Boys Ranch # 2
800
1.15
126
0.2
62
0.1
94
0.1
390
1982
60
352
Boys Ranch # 3
750
1.08
330
0.5
77
0.1
204
0.3
380
1962
60
363
Burnett 2
900
1.30
n/a
n/a
n/a
343
1960
125
313
Nob Hill Pressure Zone (HWL = 516 feet) Butterfield 480 0.69
157
0.23
65
0.1
111
0.2
2004
Condit
200
0.29
200
0.3
200
0.3
200
0.3
1979
100
395
343
Diana # 1
850
1.22
433
0.6
200
0.3
316
0.5
1949
100
242
343
Diana # 2
1,500
2.16
427
0.6
288
0.4
358
0.5
1986
150
271
373
Diana # 3
500
0.72
173
0.2
111
0.2
142
0.2
1998
60
415
365
Diana # 4
700
1.01
316
0.5
210
0.3
263
0.4
2009
Dunne # 1
1,500
2.16
147
0.2
87
0.1
117
0.2
1965
75
366
357
Dunne # 2
520
0.75
217
0.3
140
0.2
178
0.3
1997
75
343
357
Jackson # 1
400
0.58
155
0.2
106
0.2
130
0.2
Pre 1950 60
589
367
Main # 1
1,000
1.44
377
0.5
258
0.4
317
0.5
Pre 1950 125
357
358
Main # 2
1,000
1.44
409
0.6
239
0.3
324
0.5
2002
Nordstrom
850
1.22
534
0.8
326
0.5
430
0.6
1999
125
351
361
San Pedro
600
0.86
281
0.4
165
0.2
223
0.3
2002
75
351
Tennant
470
0.68
0
0.0
0
0
0
0
1979
75
344
325
Total and Firm Supply Capacity
4,428
6.4
Total Supply Capacity
13,420 19.32
2,721
3.92
3,575 5.15
Firm Capacity (Excluding largest Well Diana No. 2)
3,228
5.8
11,920 17.16
2,433
3.50
3,217 4.63
1/14/2016
Notes:
1. Source: "Well Production up to date 15 1st~2nd~3rd~4th Qtr Pro, received from City staff
2. Burnett Well is currently designated for Fire Protection only. It is not accounted for in the City's total water supply capacity.
Made with FlippingBook flipbook maker